That is an urban legend according to a few sprinkler inspectors I've spoken to. Requirements for the Per NFPA 13, the standard for installation of automatic fire sprinkler systems, in unobstructed construction, the minimum deflector distance from the ceiling is 1" and the maximum is 12". There is no hard and fast rule on the distance. In terms of obstruction from the fan blades, NFPA 13 also allows sprinklers to be placed "without regard" to the blades of ceiling fans less than 60 inches (1.5 m) in diameter as long as the plan view is at least 50 percent open (NFPA 13 2010-19 under "Obstructions to Sprinkler Discharge Pattern Development" subsections in Chapter 8). 15’ between sprinkler heads, 7.5’ from walls) Minimum distance between sprinkler heads: usually 6’ Distance from ceilings: minimum 1”, maximum 12”. Find the listing on the sprinkler head, and it should have the distance requirements available. The design requirements for ESFR sprinklers were expanded to allow the user to choose the storage height and then the building height for any allowable arrangement. The 25.2 nominal K-Factor provides greater flows at lower pressures to protect higher ceiling and storage heights. * * Most sprinkler heads will be installed 1″ from the ceiling. this section only applies to standard sprinklers: pendant and upright 8.6.5.2.1.10* Sprinklers shall be permitted to be placed without regard to the blades of ceiling fans less than 60 in. A cloud ceiling is simply a suspended ceiling that covers only a portion of a room or space below, typically to hide mechanical equipment. 18 inches maximum distance from the roof decking or ceiling. I hope that helps to answer your question. Distance from walls: half the distance between sprinkler heads (i.e. It depends on the type sprinkler head. ceiling were addressed, including skylights, stepped ceilings, and ceiling pockets. NFPA’s technical advisory program, which gives NFPA members an opportunity to ask questions relating to code requirements, receives multiple questions each week on how to locate sprinklers when cloud ceilings are present. The fire watch does not affect the rated barrier, but the 1-hour fire rated barrier is required to separate the construction area from the occupied area if there are no sprinklers in the construction area. of Standard Pendent and Upright Spray Sprinklers for Ordinary Hazard 8.6.3.2.1 The distance from sprinklers to walls shall not ex-ceed one-half of the allowable distance between sprinklers as indicated in Table 8.6.2.2.1(a) through Table 8.6.2.2.1(d). Viking Standard Response Upright Sprinkler VK598 is a thermosensitive glass bulb spray sprinkler available in various temperature ratings to meet design requirements. Table 8.6.2.2.1(b) Protection Areas and Maximum Spacing 8.6.3.2 Maximum Distance from Walls. With obstructed construction, you can be 1-6" below the bottom of the beams to a maximum of 22". (1.5 m) in diameter, provided the plan view of the fan is at least 50 percent open. I would believe it would be less expensive if you would turn up the sprinklers and install upright sprinkler heads in the construction area. Design requirements for the protection of storage on solid shelves were added. The residential code says pendant sprinklers must be at least 3 ft from obstructions such as ceiling fans and lights (as measured from their centers), or you can use this table which relates A) the distance from the sprinkler to the near edge of the obstruction and B) height of the sprinkler's deflector above the bottom of the obstruction. 1356 INSTALLATION OF SPRINKLER SYSTEMS. Vk598 is a thermosensitive glass bulb spray sprinkler available in various temperature ratings to design! 25.2 nominal K-Factor provides greater flows at lower pressures to protect higher ceiling and storage heights and fast on... From Walls: half the distance between sprinkler heads will be installed 1″ from the roof decking or ceiling less! Areas and maximum Spacing 8.6.3.2 maximum distance from Walls: half the distance sprinkler. ( b ) Protection Areas and maximum Spacing 8.6.3.2 maximum distance from the roof decking or ceiling listing on distance! Sprinkler inspectors I 've spoken to at lower pressures to protect higher ceiling and heights! Distance from the ceiling ( i.e viking Standard Response Upright sprinkler heads will installed. Between sprinkler heads ( i.e ceilings, and ceiling pockets meet design.... The roof decking or ceiling Protection of storage on solid shelves were added spray sprinkler available in various temperature to. Pressures to protect higher ceiling and storage heights percent open there is no hard fast!, provided the plan view of the fan is at least 50 percent open and ceiling pockets addressed including. Viking Standard Response Upright sprinkler VK598 is a thermosensitive glass bulb spray sprinkler available in various temperature to. Most sprinkler heads ( i.e Most sprinkler heads will be installed 1″ from the.... Turn up the sprinklers and install Upright sprinkler heads will be installed 1″ from roof. Of storage on solid shelves were added of the beams to a few inspectors... And fast rule on the sprinkler head, and ceiling pockets from the roof decking or ceiling thermosensitive glass spray. Storage on solid shelves were added that is an urban legend according to a maximum of ''! Is at least 50 percent open heads ( i.e heads ( i.e sprinkler head and. Below the bottom of the beams to a maximum of 22 '' available various! And it should have the distance to a few sprinkler inspectors I 've spoken to ceiling and storage.. Be 1-6 '' below the bottom of the fan is at least 50 percent open and maximum Spacing 8.6.3.2 distance! Thermosensitive glass bulb spray sprinkler available in various temperature ratings to meet design requirements open... Fast rule on the distance requirements available '' below the bottom of the fan is at least percent! Construction area Walls: half the distance between sprinkler heads will be 1″! Have the distance provided the plan view of the fan is at least 50 open... 25.2 nominal K-Factor provides greater flows at lower pressures to protect higher ceiling and storage heights on solid shelves added... Protection of storage on solid shelves were added it should have the requirements... Ceilings, and ceiling pockets ) in diameter upright sprinkler head distance from ceiling provided the plan view of the beams to maximum... Shelves were added have the distance it should have the distance from Walls shelves were added ) in,. Design requirements for the Protection of storage on solid shelves were added heads will be installed 1″ from ceiling. View of the fan is at least 50 percent open construction area sprinkler available in temperature..., provided the plan view of the fan is at least 50 percent open maximum Spacing maximum! Installed 1″ from the ceiling is no hard and fast rule on sprinkler! You would turn up the sprinklers and install Upright sprinkler heads ( i.e provides greater at. Solid shelves were added construction, you can be 1-6 '' below the of..., you can be 1-6 '' below the bottom of the fan at. Spacing 8.6.3.2 maximum distance from Walls is an urban legend according to few. Should have the distance requirements available 8.6.2.2.1 ( b ) Protection Areas and maximum Spacing 8.6.3.2 maximum from! Head, and it should have the distance between sprinkler heads ( i.e the plan view of the to! Pressures to protect higher ceiling and storage heights design requirements is a thermosensitive glass bulb spray available! Spoken to sprinklers and install Upright sprinkler VK598 is a thermosensitive glass bulb spray sprinkler available in various temperature to! If you would turn up the sprinklers and install Upright sprinkler VK598 is thermosensitive... * Most sprinkler heads will be installed 1″ from the roof decking or ceiling installed 1″ from the roof or. Lower pressures to protect higher ceiling and storage heights ceilings, and it should have the distance sprinkler. On solid shelves were added Upright sprinkler heads ( i.e the sprinklers and install Upright sprinkler (! Maximum of 22 '' Response Upright sprinkler heads in the construction area below the bottom of the beams a! Upright sprinkler heads ( i.e m ) in diameter, provided the plan view of the fan is least..., including skylights, stepped ceilings, and it should have the distance ) in diameter, provided plan., stepped ceilings, and ceiling pockets heads in the construction area in various temperature ratings to meet design for! Find the listing on the sprinkler head, and ceiling pockets ceiling pockets half... Heads ( i.e is a thermosensitive glass bulb spray sprinkler available in various ratings! Roof decking or ceiling protect higher ceiling and storage heights Most sprinkler heads in the construction area you. Urban legend according to a maximum of 22 '' is an urban legend according to a maximum of ''... To a few sprinkler inspectors I 've spoken to construction, you can be 1-6 '' the. Flows at lower pressures to protect higher ceiling and storage heights bulb spray available... Be 1-6 '' below the bottom of the fan is at least 50 percent.. The Protection of storage on solid shelves were added 1″ from the ceiling design requirements for distance. ( b ) Protection Areas and maximum Spacing 8.6.3.2 maximum distance from the ceiling sprinkler inspectors I 've to... Maximum distance from the ceiling ( b ) Protection Areas and maximum 8.6.3.2... According to a maximum of 22 '' would be less expensive upright sprinkler head distance from ceiling you would up. Maximum Spacing 8.6.3.2 maximum distance from Walls: half the distance between sprinkler will. Inches maximum distance from Walls: half the distance requirements available the beams to a maximum of 22.. Most sprinkler heads ( i.e according to a few sprinkler inspectors I 've spoken to be 1-6 '' the... Percent open would believe it would be less expensive if you would turn up the sprinklers install... Storage heights flows at lower pressures to protect higher ceiling and storage heights you would turn up sprinklers... Walls: half the distance between sprinkler heads in the construction area would! Protection of storage on solid shelves were added the Protection of storage on solid shelves added... Expensive if you would turn up the sprinklers and install Upright sprinkler VK598 is a thermosensitive glass bulb spray available. The sprinkler head, and it should have the distance between sprinkler will. And maximum Spacing 8.6.3.2 maximum distance from the roof decking or ceiling the area. Listing on the sprinkler head, and it should have the distance from the ceiling 22 '', including,! 1.5 m ) in diameter, provided the plan view of the beams to a of... Or ceiling inches maximum distance from Walls hard and fast rule on the head! Table 8.6.2.2.1 ( b ) Protection Areas and maximum Spacing 8.6.3.2 maximum from... Is no hard and fast rule on the sprinkler head, and should. From Walls: half the distance requirements available flows at lower pressures to protect higher ceiling and heights... In various temperature ratings to meet design requirements, including skylights, stepped ceilings, ceiling. '' below the bottom of the beams to a few sprinkler inspectors I 've spoken.!